IR Images
Sample Report Compression Fitting
Comprehensive Infrared Report
Your Name
Problem 5
Component  "B" Phase, Compression Fitting
Equipment Panel EM
Location Main Electrical Room
Possible Problem Bad Compression fitting on Aluminum wire
Special Note
Date of Survey December 22, 1999 Time exception was located 0914
Survey By Dale Southworth Certification Number 3018

Temperature Analysis of Infrared Image

Problem Temperature
141
Degrees Fahrenheit
61
Degrees Centigrade
Ambient Temperature
83
Degrees Fahrenheit
28
Degrees Centigrade
Temperature Rise
58
Degrees Fahrenheit
32
Degrees Centigrade

Temperature Rise Classification Table

Minor Level Monitor
1-18 F°
.5-9.5 C°
Intermediate Level Repair Next Scheduled Maintenance 
19-63F°
10.5-35 C°
Serious Level Schedule For Repair As Soon As Possible
64-128 F°
35.5-71.1 C°
CRITICAL LEVEL Critical, Repair Immediately 
>129 F°
>71.6 C°
When phase is stated in this report, unless otherwise indicated or marked, "A" top, "B" center and "C" Bottom and from the front of the equipment "A" left, "B" center and "C" right. This is to simplify  this report and reduce the chance for errors.