Sample Report Motor Bearing |
![]() |
Comprehensive Infrared Report |
Your Name |
Problem 4 | |||
Component | Pump End Motor Bearing | ||
Equipment | Pump "P2" | ||
Location | Boiler Room | ||
Possible Problem | Bad Bearing, Worn Thrust Spacer or Lubrication Problem | ||
Special Note | |||
Date of Survey | December 22, 1999 | Time exception was located | 0900 |
Survey By | Dale Southworth | Certification Number | 3018 |
Temperature Analysis of Infrared Image
Problem Temperature |
139
|
Degrees Fahrenheit |
59
|
Degrees Centigrade |
Ambient Temperature |
78
|
Degrees Fahrenheit |
26
|
Degrees Centigrade |
Temperature Rise |
61
|
Degrees Fahrenheit |
34
|
Degrees Centigrade |
Temperature Rise Classification Table
Minor Level | Monitor |
1-18 F°
|
.5-9.5 C°
|
Intermediate Level | Repair Next Scheduled Maintenance |
19-63F°
|
10.5-35 C°
|
Serious Level | Schedule For Repair As Soon As Possible |
64-128 F°
|
35.5-71.1 C°
|
CRITICAL LEVEL | Critical, Repair Immediately |
>129 F°
|
>71.6 C°
|
When phase is stated in this report, unless otherwise indicated or marked, "A" top, "B" center and "C" Bottom and from the front of the equipment "A" left, "B" center and "C" right. This is to simplify this report and reduce the chance for errors.